CHAPTER 6: PLUMBING ELEMENTS AND FACILITIES
TECHNICAL
CHAPTER 6: PLUMBING ELEMENTS AND FACILITIES
601 General
601.1 Scope.
The provisions of Chapter 6 shall apply where required by Chapter 2 or where referenced
by a requirement in this document.
602 Drinking Fountains
602.1 General.
Drinking fountains shall comply with 307 and 602.
602.2 Clear Floor Space.
Units shall have a clear floor or ground
space
complying with 305 positioned
for a forward approach and centered on the unit.
Knee and toe clearance complying with 306 shall be
provided.
EXCEPTION:
A parallel approach complying with 305 shall be permitted at units for
children's use
where the spout is 30 inches (760 mm) maximum above the finish floor or ground and is 3½ inches
(90 mm) maximum from the front edge of the unit, including bumpers.
602.3 Operable Parts.
Operable parts
shall comply with 309.
602.4 Spout Height.
Spout outlets shall be 36 inches (915 mm) maximum above the finish floor or
ground.
602.5 Spout Location.
The spout shall be located 15 inches (380 mm) minimum from the vertical
support and 5 inches (125 mm) maximum from the front edge of the unit, including bumpers.
602.6 Water Flow.
The spout shall provide a flow of water 4 inches (100 mm) high minimum and shall
be located 5 inches (125 mm) maximum from the front of the unit.
The angle of the water stream shall
be measured horizontally relative to the front face of the unit.
Where spouts are located less than 3
inches (75 mm) of the front of the unit, the angle of the water stream
shall be 30 degrees maximum.
Where spouts are located between 3 inches (75 mm) and 5 inches (125 mm) maximum from the front of
the unit, the angle of the water stream shall be 15 degrees maximum.
Figure 602.5
Drinking Fountain Spout Location
2010 Standards: Titles II and III
-
159
Department of Justice